17
3.2 Hydraulic variant 1
Solar charging of tank 1.
(Tank type can be chosen, warm water/
heating / swimming pool)
Connections hydraulic 1:
Code
Adju-
ster
Function Setting
range
Factory
setting
Unit Basic set.
Dat.:
-
8-62
Set temperature tank 1, normal
0÷90 60 °C
8-63
Setting temperature differentials for
thermal circuit1
1÷30 2 K
8-85
Setting value collector pump 1, in ma-
nual operation
0÷100 0 %
1
4-06
Hydraulic variants
1÷9 1 -
4-20
Addressing of eBUS
1÷16 16 -
4-36
eBUS charging
on/off off -
5-04
Legionella protection temperature
60÷80 60 °C
5-14
Legionella protection function
0÷9 0 -
8-01
Increase collector tank for charging
ON
0÷50 15 K
8-02
Increase collector tank for charging
OFF
0÷50 5 K
8-15
Start-up help pipe collector
on/off on -
8-20
P range (Xp) collector controller pump
steering
10÷50 20 K
8-21
Response time (Tn) collector control-
lers
0÷30 10 min
8-22
Derivative time (Tv) collector control-
ler
0÷10 0 min
8-30
Solar nominal performance collector 1
1÷50 8 kW
8-35
Min. set value collector pump 1
5÷100 50 %
8-37
Volume flow coll. pump 1 at 100% set
value
1÷50 2
l/min
8-50
Basic strategy solar charging
0÷4 3 -
8-51
Change-over solar charging (high en-
ergy levels)
30÷100 50 %
8-55
Tank type, tank 1
0÷4 0 -
8-59
Maximum temperature, tank 1
10÷90 80 °C
8-60
Protective temperature tank 1
10÷95 90 °C
8-64
Set value charging temperature
increase, tank 1
5÷50 20 K
SET
B1
B2
3
L N N 1 2 N N 3
B1 B2
TT
Storage tank 1
sensor bottom
Pump
solar charging
Not
used
Not
used
Voltage supply
230 V / 50 Hz
Collector 1
sensor
High voltage
Sensors
Komentarze do niniejszej Instrukcji