RM Solar S Class 20 Instrukcje Operacyjne Strona 13

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 12
13
1.6 Adjuster code 1
Adju-
ster
Hy-
draulic
Function Setting
range
Factory
setting
Unit Basic setting
Dat.:
Adaptation
Dat.:
08-55 all Tank type, tank 1 0÷4 0 -
0 = Hot water tank All charging strategies are possible. According to application, the set-
tings for the change-over to alternating operation must be adjusted.
(Adjuster 8-65 and Adjuster 8-66)
2 = Heating tank If the tank set value is set below 20°C, this is understood to be sum-
mer operation. The tank set value will be lowered to the frost tempe-
rature of 10 °C.
4 = Swimming pool Not included in alternating operation
08-59 all Maximum temperature, tank 1 10÷90 80 °C
If the temp. at the tank sensor rises above the set value, solar charging for this tank is disabled.
With active overheating protection (Adjuster 8-05) this limiting value is ignored.
08-60 all Protective temperature tank 1 10÷95 90 °C
If the temp. at the tank sensor rises above the set value, solar charging is disabled, even if the overheating protec-
tion is active.
08-64 all
Set value charging temperature
increase, tank 1
5÷50 20 K
Minimum increase which is demanded at the collector sensor for charging. This increase always refers to the tank
sensor.
SET
A0805
Przeglądanie stron 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 ... 23 24

Komentarze do niniejszej Instrukcji

Brak uwag